Troubleshooting and Problem Solving
DataDirect Networks EF2800 FC RAID Storage System User Guide (V 1.0)
151
10.4.4 Thermal Alarm
Symptom Cause Action
1. Ops panel FAULT
LED turns amber.
2. An amber LED on
one or more power
supply/cooling
modules.
3. Audible alarm is
activated.
4. Air temperature
exiting PSU above
55°C.
If the internal
temperature
measured in the
airflow through
the enclosure
exceeds a pre-set
threshold a
thermal alarm is
activated.
1. Check local ambient
environment temperature
is below the upper 40°C
specification.
2. Check the installation for
any airflow restrictions at
either the front or rear of
the enclosure. A minimum
gap of 1" (25mm) at the
front and 2" (50mm) at the
rear is recommended.
3. Check for restrictions
due to dust build-up; clean
as appropriate.
4. Check for excessive re-
circulation of heated air
from rear to the front. Use
in a fully enclosed rack
installation is not
recommended.
5. If possible shutdown the
enclosure and investigate
the problem before
continuing.